4 alarm word and warning word – GE Industrial Solutions AF-650 GP DeviceNet User Manual

Page 55

Advertising
background image

8.1.4 Alarm Word and Warning Word

Alarm word and Warning word are shown on the display in Hex format. If there is more than one warning or alarm, a sum of all warnings or alarms will be shown.
Alarm word and warning word can also be displayed using the field bus in par. DR-05 Main Actual Value [%].

AF-650 GP or AF-600 FP

Bit (Hex)

Alarm word
(par. DR-90 Alarm Word)

Alarm no.

Major /
minor alarm

Recoverable /
unrecoverable alarm

00000001

Unused

-

-

-

00000002

Drive over temperature

29

Major

Recoverable

00000004

Earth fault

14

Major

Unrecoverable

00000008

Unused

-

-

-

00000010

Control word timeout

18

Minor

Recoverable

00000020

Over current

13

Major

Unrecoverable

00000040

Torque limit

12

Major

Recoverable

00000080

Motor thermistor over temp.

11

Major

Recoverable

00000100

Motor Thermal Electronic Overload
over temperature

10

Major

Recoverable

00000200

Drive overloaded

9

Major

Recoverable

00000400

DC link under voltage

8

Major

Recoverable

00000800

DC link over voltage

7

Major

Recoverable

00001000

Short circuit

16

Major

Unrecoverable

00002000

Inrush fault

33

Major

Recoverable

00004000

Mains phase loss

4

Major

Unrecoverable

00008000

Auto Tune not OK

50

Major

Recoverable

00010000

Live zero error

2

Major

Recoverable

00020000

Internal fault

38

Major

Unrecoverable

00040000

Brake resistor power limit

26

Major

Unrecoverable

00080000

Motor phase U is missing

30

Major

Unrecoverable

00100000

Motor phase V is missing

31

Major

Unrecoverable

00200000

Motor phase W is missing

32

Major

Unrecoverable

00400000

Fieldbus comm. fault

34

Major

Recoverable

00800000

24 V supply fault

47

Major

Unrecoverable

01000000

Mains failure

36

Major

Recoverable

02000000

1.8 V supply fault

48

Major

Unrecoverable

04000000

Brake resistor short circuit

25

Major

Recoverable

08000000

Brake chopper fault

27

Major

Recoverable

10000000

Unused

-

-

-

20000000

Unused

-

-

-

40000000

Unused

-

-

-

80000000

Unused

-

-

-

AF-600FP /650 GP DeviceNet Operating Instructions

54

8

Advertising