Bit 09 = "1" means that ramp 2 (par. SP-76 Accel/Decel Time 2 Type to par. SP-81 Decel Time 2 S-ramp Ratio at Decel. Start) is active.

Bit 10, Data not valid/Data valid:
Is used to tell the frequency converter whether the control word is to be used
or ignored. Bit 10 = 0 causes the control word to be ignored, Bit 10 = 1 causes
the control word to be used. This function is relevant, because the control
word is always contained in the telegram, regardless of which type of tele-
gram is used, i.e. it is possible to turn off the control word if you do not wish
to use it in connection with updating or reading parameters.

Bit 11, Relay 01:
Bit 11 = "0" Relay not activated.
Bit 11 = "1" Relay 01 activated, provided Control word bit 11 has been chosen
in par. E-24 Function Relay.

Bit 12, Relay 04:
Bit 12 = "0" Relay 04 has not been activated.
Bit 12 = "1" Relay 04 has been activated, provided Control word bit 12 has
been chosen in par. E-24 Function Relay.

Bit 13/14, Selection of set-up:
Bits 13 and 14 are used to choose from the four menu set-ups according to
the table to the right:

Set-up

Bit 14

Bit 13

1

0

0

2

0

1

3

1

0

4

1

1

The function is only possible when Multi-Set-ups is selected in par. K-10 Active Set-up.

NB!
In par. O-55 Set-up Select a selection is made to define how Bits 13/14 gate with the corresponding function on the digital inputs.

Bit 15 Reverse:
Bit 15 = 0 causes no reversing.
Bit 15 = 1 causes reversing.