Alarms and events description and system troubleshooting guide

227

A

Caution Messngr Not Receiving
From CPUB

Messenger reports that it is not receiving
data from CPU B

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and the
CPU B. Verify that CPU B is powered on and
operating.

System OK Receiving Broadcast
From CPUA

Messenger reports that it is receiving data
from CPU A

System OK Receiving Broadcast
From CPUB

Messenger reports that it is receiving data
from CPU B

Test Mode Initiated From Test
Kit

Messenger reports that test mode has been
initiated with the test kit

Test Mode Ended From Test Kit

Messenger reports that test mode has ended

Protection Suspended GF From
Test Kit

Messenger reports that ground fault
functionality is to be suspended

Protection Resumed GF From
Test Kit

Messenger reports that ground fault
functionality can resume

Attention Compartment ID
Button Missing

Messenger reports that it has detected that
the compartment ID button is missing

See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.

Note Messngr Error 5

Compartment ID Button contains valid
configuration data, but EEPROM copy is bad

See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.

Caution Check Compartment ID
Button Connection

Messenger reports that the compartment ID
button connection needs to be checked

See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.

Attention Messngr Error 1
Replace ASAP

Messengr reports that its application flash
memory has a CRC error and should be
replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr Error 2
Replace ASAP

Messengr reports that its boot flash memory
has a CRC error and should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr Error 3
Replace ASAP

Messenger reports that it has an analog IOC
error and should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr Error 4
Replace ASAP

Messenger reports that it is not calibrated
and should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

CPU Status

Power On

CPU has powered on

Discrete IO Test Mode Initiated

Test mode for discrete I/O has been initiated

Discrete IO Test Mode Ended

Test mode for discrete I/O has ended

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips