background image

Single Point Relay protection

63

5

5.2.2.4 Alarm settings

Relay Enabled: Select Enabled to enable the relay.

Pickup: Adjust the overvoltage pickup from 105% to 125% in increments of 1% from the Pickup
Setting drop-down menu.

Delay: Adjust the overvoltage delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:

• Operate if any one phase is below the pickup threshold
• Operate if any two phases are below the pickup threshold
• Operate if all three phases are below the pickup threshold

Figure 5-5 Settings for Overvoltage Relay