Single Point Relay protection
63
5
5.2.2.4 Alarm settings
Relay Enabled: Select Enabled to enable the relay.
Pickup: Adjust the overvoltage pickup from 105% to 125% in increments of 1% from the Pickup
Setting drop-down menu.
Delay: Adjust the overvoltage delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.
Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:
• Operate if any one phase is below the pickup threshold
• Operate if any two phases are below the pickup threshold
• Operate if all three phases are below the pickup threshold
Figure 5-5 Settings for Overvoltage Relay