3 alarm settings – GE Industrial Solutions Entellisys System User Manual User Manual

Page 60

Advertising
background image

Single point functions

60

5

Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:

• Operate if any one phase is below the pickup threshold
• Operate if any two phases are below the pickup threshold
• Operate if all three phases are below the pickup threshold

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage.

Blocking Voltage Setting: Adjust the blocking voltage from 5% to 75% in increments of 1%
using the Setting drop-down menu in the Blocking Voltage section.

Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.

5.2.1.3 Alarm settings

Relay Enabled: Select Enabled to enable the alarm relay.

Curve Type: Select either Constant time curve or Inverse time curve from the Curve Type
drop-down menu.

Pickup: Adjust the undervoltage pickup from 50% to 95% in increments of 1% from the Pickup
Setting drop-down menu.

Delay: Adjust the undervoltage delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:

• Operate if any one phase is below the pickup threshold
• Operate if any two phases are below the pickup threshold
• Operate if all three phases are below the pickup threshold

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage.

Blocking Voltage Setting: Adjust the blocking voltage from 5% to 75% in increments of 1%
using the Setting drop-down menu in the Blocking Voltage section.