Alarms and events description and system troubleshooting guide

229

A

Reduced Let Thru Mode Initiated Reduced Let Thru Mode has been initiated,

CPU is using its group 0 settings

Reduced Let Thru Mode Ended

Reduced Let Thru Mode has ended

Adv Protection Default To Bus
Cfg 1 Brkr Err

Topology breaker is in an undefined state (i.e.
not open and not closed), therefore system
topology cannot be determined and CPU has
defaulted to bus configuration 1

Breaker service issue, contact GE Post Sales
Service (see

How to contact us on page 2

).

System Topology State Change

System topology has changed

Adv Protection Default To Bus
Cfg 1 File Err

Configuration files that define the system
topology states is bad or missing, and the
CPU has defaulted to bus configuration 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Discrete IO Disabled Invalid Cfg
Card 1

CPU is unable to configure I/O for Card 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Discrete IO Disabled Invalid Cfg
Card 2

CPU is unable to configure I/O for Card 2

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Discrete IO Disabled Card In
Wrong Slot

Only one I/O card detected, and it is plugged
into PMC1 instead of PMC0

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution System Topology
Defaulted

The system has reverted to the default
topology (topology 1). This occurs when the
CPU is unable to determine the state of one
or more of the topology breakers.

Breaker service issue, contact GE Post Sales
Service (see

How to contact us on page 2

).

Attentn PT Sources Defaulted
Invalid Cfg File

The file that describes the PT sources for
each breaker for each topology is invalid.
Each breaker is now using its own voltage
information, if any (this is the default state).

Contact GE Post Sales Service (see

How to

contact us on page 2

).

PT Throwover Has Occurred

Something has caused the system topology
to change (typically a topology breaker has
opened or closed), and the PT sources for
some breakers may have changed.

Messngr Decommissioned
Manual Command

Messenger was decommissioned by a
command received over modbus

Messngr Commissioned Manual
Command

Messenger was commissioned

ZSI Zone 1…4 Operation

ZSI has udpated the delay times for functions
in zone 1…4

ZSI Zone 1…4 Enabled

ZSI functionality for zone 1…4 has been
enabled

ZSI Zone 1…4 Disabled

ZSI functionality for zone 1…4 has been
disabled

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips