10.2 General Technical Data
Mains supply (L1, L2, L3):
Supply voltage
200-240V
±10%, 380-480V ±10%, 525-600V ±10%,
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency
50/60Hz
±5%
Max. imbalance temporary between mains phases
3.0% of rated supply voltage
True Power Factor ()
≥ 0.9 nominal at rated load
Displacement Power Factor (cos) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤ unit size 1x
maximum twice/min.
Switching on input supply L1, L2, L3 (power-ups)
≥ unit sizes 2x, 3x
maximum once/min.
Switching on input supply L1, L2, L3 (power-ups)
≥ unit sizes 4x, 5x, 6x
maximum once/2 min.
Environment according to EN60664-1
overvoltage category III / pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W):
Output voltage
0 - 100% of supply voltage
Output frequency
0 - 1000 Hz
*
Switching on output
Unlimited
Accel/Decel Times
1 - 3600 sec.
*
Dependent on power size.
Torque characteristics:
Starting torque (Constant torque)
maximum 110% for 1 min.
*
Starting torque
maximum 135% up to 0.5 sec.
*
Overload torque (Constant torque)
maximum 110% for 1 min.
*
*Percentage relates to the frequency converter's nominal torque.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
150 m
Max. motor cable length, unscreened/unarmoured
300 m
Max. cross section to motorand mains*
Maximum cross section to control terminals, rigid wire
1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross section to control terminals, flexible cable
1 mm
2
/18 AWG
Maximum cross section to control terminals, cable with enclosed core
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
* See 10.1 Power-dependent Specifications for more information!
Digital inputs:
Programmable digital inputs
4 (6)
Terminal number
18, 19, 27
1)
, 29, 32, 33,
Logic
PNP or NPN
Voltage level
0 - 24V DC
Voltage level, logic'0' PNP
< 5V DC
Voltage level, logic'1' PNP
> 10V DC
Voltage level, logic '0' NPN
> 19 V DC
Voltage level, logic '1' NPN
< 14V DC
Maximum voltage on input
28V DC
Input resistance, R
i
approx. 4k
Ω
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Specifications
AF-600 FP Operating Instructions
66