2 ce compliance – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual
Page 75
10.3.2 CE Compliance
Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the drive voltage rating. With the proper fusing the drive short circuit current rating (SCCR) is
100,000 Arms.
AF-600 3-phase
Recommended fuse size
Recommended max fuse
Recommended circuit breaker
Max trip level
[HP]
[A]
1
gG-16
gG-25
PKZM0-25
25
2
3
5
gG-20
gG-32
7,5
gG-50
gG-63
PKZM4-50
50
10
15
20
gG-80
gG-125
NZMB1-A100
100
25
30
gG-125
gG-150
NZMB2-A200
150
40
aR-160
aR-160
50
aR-200
aR-200
NZMB2-A250
250
60
aR-250
aR-250
Table 10.7 200-240V, IP20/Open Chassis
AF-600 3-phase
Recommended fuse size
Recommended max fuse
Recommended circuit breaker
Max trip level
[HP]
[A]
1
gG-20
gG-32
PKZM0-25
25
2
3
5
7,5
gG-63
gG-80
PKZM4-63
63
10
15
20
gG-80
gG-100
NZMB1-A100
100
25
gG-125
gG-160
NZMB2-A200
160
30
40
aR-160
aR-160
50
aR-200
aR-200
NZMB2-A250
250
60
aR-250
aR-250
Table 10.8 200-240V, IP55/Nema 12
Specifications
AF-600 FP Operating Instructions
72
10
0