ALARM 70, Illegal Drive Configuration
The current control board and power board combination is illegal.

Warning 73, Safe stop auto restart
Safe stopped. Note that with automatic restart enabled, the motor may start when the fault is cleared.

ALARM 79, Illegal power section configuration
The scaling card is the incorrect part number or not installed. Also, the MK102 connector on the power card is not installed.

ALARM 80, Drive Restored to Factory Settings
Parameter settings are restored to factory settings after a manual reset.

WARNING 81, CSIV corrupt
CSIV file has syntax errors.

WARNING 82, CSIV parameter error
CSIV has failed to record a parameter.

ALARM 91, Analog input 54 wrong settings
Switch S202 must be set in the position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54.

ALARM 92, No flow
A no-load situation has been detected in the system. See parameter group AP-2#.

ALARM 93, Dry pump
A no-flow situation and high speed indicate that the pump has run dry. See parameter group AP-2#.

ALARM 94, End of curve
Feedback stays lower than the setpoint which may indicate leakage in the pipe system. See parameter group AP-5#.

ALARM 95, Broken belt
Torque is below the torque level set for no load, indicating a broken belt. See parameter group AP-6#.

ALARM 96, Start delayed
Motor start has been delayed due to short-cycle protection active. See parameter group AP-7#.

WARNING 97, Stop delayed
Stopping the motor has been delayed due to short cycle protection is active. See parameter group AP-7#.

WARNING 98, Clock fault
Clock Fault. The time is not set or the RTC clock (if mounted) has failed. See parameter group K-7#.

WARNING 200, Fire mode
The input command fire mode is active. See parameter group FB-0#.

WARNING 201, Fire mode was active
Fire mode has been active. See parameter group K-7#.

WARNING 202, Fire mode limits exceeded
One or more warranty voiding alarms have been suppressed during fire mode operation. See parameter group K-7#.

ALARM 243, Brake IGBT
This alarm is only for 6x Frame frequency converters. It is equivalent to Alarm 27. The report value in the alarm log indicates which power module generated the
alarm:

1 = left most inverter module.

2 = middle inverter module in 62 or 64 drive.

2 = right inverter module in 61 or 63 drive.

3 = right inverter module in 62 or 64 drive.

5 = rectifier module.

ALARM 244, Heatsink temperature
This alarm is only for 6x Frame frequency converters. It is equivalent to Alarm 29. The report value in the alarm log indicates which power module generated the
alarm:

1 = left most inverter module.

2 = middle inverter module in 62 or 64 drive.

2 = right inverter module in 61 or 63 drive.

3 = right inverter module in 62 or 64 drive.

5 = rectifier module.

AF-650 GP and AF-600 FP High Power Service Manual