Galaxy Power System Verification Procedures

4 - 4 Replacement Procedures

Issue 3 January 2008

Memory Backup Battery Replacement for SC/SCF Controller,
continued

Restore System

Configuration

Step

Action

1

Log in and begin an EasyView session using the previously
modified connection profile.

2

Open the File menu and click on Restore. Select the
configuration file you saved when you performed the
Backup operation. Click OK. EasyView displays the status
of the backup. Click OK when the Restore operation is
complete.

3

Open the Configure menu and click on Configure
Passwords. Change the passwords from the default setting to
the appropriate password for your site.

4

Open the Options menu and click on Setup Sites. Select your
connection profile from the Site list. Click Modify. Change
the passwords to those from the previous step. Click OK.
Click Close.

5

Open the Connect menu and select Disconnect to end the
EasyView session.