GE Industrial Solutions MX350 Communications Guide User Manual

Page 43

Advertising
background image

COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

39

43172

0C63

Auto Mode Shed kW Bypass

0

1

1

---

FC126

0

1

43173

0C64

Reserved

---

---

---

---

---

---

1

to

to

Reserved

---

---

---

---

---

---

1

43178

0C69

Reserved

---

---

---

---

---

---

1

ATS CONTROL TIMERS

43179

0C6A

Time Delay to Preferred Source 0

600

1

---

F24

5

1

43180

0C6B

Time Delay to Alternate Source 0

600

1

---

F24

5

1

43181

0C6C

Gen Run Timer Value

0

3600

1

---

F24

0

1

43182

0C6D

Time Delay for Gen Sag

0

30

1

---

F24

0

1

43183

0C6E

Delay for Generator Start

0

15541

1

---

F24

3

1

43184

0C6F

S2 Failure Response Delay (P2) 0

15540

1

---

F24

3

1

43185

0C70

Time Delay to Preferred Source 0

15540

1

---

F24

1800

1

43186

0C71

Reserved

---

---

---

---

---

---

1

43187

0C72

Delay for Engine Cooldown

0

3600

1

---

F24

300

1

43188

0C73

U2 Timer Value

0

3600

1

---

F24

600

1

43189

0C74

Time Delay to Alternate Source 0

15540

1

---

F24

3

1

43190

0C75

Pre Load Control 1 (LC1) Timer 0

3600

1

---

F24

0

1

43191

0C76

Pre Load Control 2 (LC2) Timer 0

3600

1

---

F24

0

1

43192

0C77

Pre Load Control 3 (LC3) Timer 0

3600

1

---

F24

0

1

43193

0C78

Pre Load Control 4 (LC4) Timer 0

3600

1

---

F24

0

1

43194

0C79

Pre Load Control 5 (LC5) Timer 0

3600

1

---

F24

0

1

43195

0C7A

Pre Load Control 6 (LC6) Timer 0

3600

1

---

F24

0

1

43196

0C7B

Post Load Control 1 (LC1) Timer 0

3600

1

---

F24

0

1

43197

0C7C

Post Load Control 2 (LC2) Timer 0

3600

1

---

F24

0

1

43198

0C7D

Post Load Control 3 (LC3) Timer 0

3600

1

---

F24

0

1

43199

0C7E

Post Load Control 4 (LC4) Timer 0

3600

1

---

F24

0

1

43200

0C7F

Post Load Control 5 (LC5) Timer 0

3600

1

---

F24

0

1

43201

0C80

Post Load Control 6 (LC6) Timer 0

3600

1

---

F24

0

1

43202

0C81

Reserved

---

---

---

---

---

---

1

to

to

Reserved

---

---

---

---

---

---

1

43207

0C86

Reserved

---

---

---

---

---

---

1

ATS R50

43208

0C87

Max Frequency Difference

0

500

1

Hz

F3

500

1

43209

0C88

Sync Phase Angle Limit

0

21

1

°

F1*

10

1

43210

0C89

Reserved

---

---

---

---

---

---

1

to

to

Reserved

---

---

---

---

---

---

1

43233

0CA0

Reserved

---

---

---

---

---

---

1

ATS SOURCE 1 CONFIGURATION

43234

0CA1

S1 Overfreq Fail

501

631

1

Hz

F2*

631

1

43235

0CA2

S1 Overfreq Restore

500

629

1

Hz

F2

629

1

43236

0CA3

S1 Overvolt Fail

105

111

1

%

F1*

110

1

43237

0CA4

S1 Overvolt Restore

103

108

1

%

F1

105

1

43238

0CA5

S1 Underfreq Fail

450

599

1

Hz

F2

590

1

43239

0CA6

S1 Underfreq Restore

451

600

1

Hz

F2

595

1

43240

0CA7

S1 Undervolt Fail

75

99

1

%

F1

80

1

43241

0CA8

S1 Undervolt Restore

85

100

1

%

F1

90

1

Modbus

Hex

Description

Min

Max

Step

Units

Format Default

Size in

Words