MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

COMMUNICATIONS GUIDE

0xDDC2

S2 CB Closed

0xDE02

S2 CB Open

0xDE42

S2 CB Relay Lockout

0xDEC2

S2 Remote Load Shed

0xDE82

Remote Timer Bypassed

FC140

16 bits

Interlock Function

0

Disabled

1

Fault

2

Alarm

FC141

16 bits

Timer Type

0

Millisecond

1

Second

2

Minute

FC142

16 bits

FlexLogic Bit Field EEETTTTTTTSSSSSS S-Bits denotes

the element state or Operator specific data Number of

inputs T-Bits denote Flex logic Operands and

Parameters or when one of the E bits are set they

denote specific details for the Element Type E-Bits

0x0000

OFF

0x0001

ON

0x0040

Contact Inputs

0x0080

Virtual Inputs

0x00C0

Virtual Outputs

0x01C0

Remote Inputs

0x0380

Insert

0x0400

End

0x0440

NOT

0x0480

XOR

0x04C0

LATCH

0x0500

OR

0x0540

AND

0x0580

NOR

0x05C0

NAND

0x0600

TIMER

0x0640

ASSIGN

0x8000

Fault

0xA000

Alarm

0xC000

Control

FC144

32 bits

LED Status

Bit 0

Alarm Red

Bit 2

TD Active Red

Bit 4

Xfer Inhibit Red

Bit 9

S1 Available Green

Bit 15

S1 Connected Green

Bit 26

S2 Available Red

Bit 28

S2 Connected Red

FC145

16 bits

Element Status 1

Bit 0

Level

Code

Type

Definition