GE Industrial Solutions MX350 Communications Guide User Manual
Page 57
COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE
53
Bit 1
Operated
Bit 2
Latched
FC147
16 bits
LED Intensity
0
Level 1
3
Level 2
6
Level 3
9
Level 4
12
Level 5
15
Level 6
FC148
16 bits
Trigger Mode
0
Retrigger
1
One-Shot
FC150
32 bits
IP Address
IP address, subnet mask or default gateway Each byte in this register represents one octet of an IP
address For example: 0x015EDA1F represents address 19421831
FC158
16 bits
ATS Source Status
0
Not Accepted
1
Accepted
FC159
16 bits
ATS Type
0
Std (Open) Trans
1
Std (Open) Bypass
2
Delayed Trans
3
Delayed Bypass
4
Closed Trans
5
Closed Trans Bypass
6
Delayed CB Type
7
Closed CB Type
FC161
16 bits
ATS Source
0
S1
1
S2
FC163
16 bits
Exerciser Period
0
OFF
1
Daily
2
Weekly
3
14 Days
4
28 Days
5
365 Days
FC165
16 bits
ATS Rated Amperage
0
40 A
1
80 A
2
100 A
3
150 A
4
200 A
5
225 A
6
260 A
7
400 A
8
600 A
Code
Type
Definition