44

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

COMMUNICATIONS GUIDE

Format codes

Code

Type

Definition

F1

16 bits

UNSIGNED VALUE

Example: 1234 stored as 1234
F2

16 bits

UNSIGNED VALUE, 1 DECIMAL PLACE

Example: 123.4 stored as 1234
F3

16 bits

UNSIGNED VALUE, 2 DECIMAL PLACES

Example: 12.34 stored as 1234
F4

16 bits

2’s COMPLEMENT SIGNED VALUE

Example: -1234 stored as -1234 i.e. 64302
F6

16 bits

2’s COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACES

Example: -12.34 stored as -1234 i.e. 64302
F9

32 bits

UNSIGNED LONG VALUE

1st 16 bits

High Order Word of Long Value

2nd 16 bits

Low Order Word of Long Value

Example: 123456 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F10

32 bits

UNSIGNED LONG VALUE, 1 DECIMAL PLACE

1st 16 bits

High Order Word of Long Value

2nd 16 bits

Low Order Word of Long Value

Example: 12345.6 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F13

32 bits

2’s COMPLEMENT SIGNED LONG VALUE, 1 DECIMAL

PLACE

1st 16 bits

High Order Word of Long Value

2nd 16 bits

Low Order Word of Long Value

Example: -12345.6 stored as -123456
i.e. 1st word: FFFE hex, 2nd word: 1DC0 hex
F15

16 bits

HARDWARE REVISION

0

Prototype

1

A

2

B

3

C

4

D

5

E

6

F

7

G

8

H

9

I

10

J

11

K

12

L

13

M

14

N

15

O

16

P

17

Q