CHAPTER 5: SETPOINTS

CONTROL

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

5–19

The Interlock screen lets the user enable interlock functions and define their parameters.
Programmable parameters for each interlock are a corresponding name, a function (fault
or alarm), an associated time delay, and the definition of the interlocks healthy state. Once
an interlock has been enabled on this screen, a corresponding input can be set up for this
element on Setpoints\Config\Inputs screen.
The following picture shows a typical interlock setup:

Figure 12: Typical interlock setup

Alarms

The Alarms screen lets the user enable alarm features and define the setpoints for
triggering these alarms as well as associated time delays. Any configured alarm can be
linked to a programmable output on the Setpoints\Config\Outputs\Alarms screen for
customer use.

NOTE

NOTE:

When a Power Factor alarm activates, you can determine whether it is a lead or lag Power
Factor alarm by going to either the Home > Values > Summary, or Home > Values >
Power
screen.

.