Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

13 - 12 Troubleshooting Millennium Systems

Issue 10 February 2008

RECT

MIN

Rectifier Fail

ALM

ICS
IP5
IP6
IP7
InF
FSE
LS

Internal rectifier
failure

1. Place the ac circuit

breaker for the
rectifier in the OFF
position.

2. Remove the

rectifier from the
shelf.

3. Wait for 30 seconds

or until all front
panel display LEDs
have extinguished.

4. Replace the

rectifier.

5. Return the ac

breaker to the ON
position.

6. Place the rectifier

ON/STBY switch
into the ON
position.

7. If the problem is not

corrected, replace
the rectifier.

RECT

MIN

Rectifier Fail

ALM

LO

Low output
voltage:
•Excessive

output current

•Internal rectifier

failure

1. Toggle the ON/

STBY switch into
the STBY position
and then back into
the ON position.

2. If the problem is not

corrected, replace
the rectifier.

Table 13-E: Rectifier Related Alarms (Continued)

(See Figures 12-4 and 12-6)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)