GE Industrial Solutions GPS 4848_100 Users Guide (single rectifier shelf) User Manual
Page 56

Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later
9 - 2 Specifications
Issue 10 February 2008
Physical
Width, Depth
600 mm, 600 mm (23.6 in. x 23.6 in.)
Weight (approximate, per cabinet)
250 kg (551 lbs.)
Height (cabinet only)
2134 mm (84.0 in.)
Height (cabinet with link bus bar)
2274 mm (89.5 in.)
Environmental
Maximum Input Current, per cabinet 120 amperes per phase, 3-wire
Heat Release, per cabinet
(54Vdc 24Adc)
Per Rectifier
4 Rectifiers
6 Rectifiers
7 Rectifiers
8 Rectifiers
595A/LTA
595B/LTB
1,030W (3,520 BTU/hr)
1,180W (4,050 BTU/hr)
4,120W (14,100 BTU/hr) 4,720W (16,120 BTU/hr)
6,180W (21,100 BTU/hr) 7,080W (24,170 BTU/hr)
7,210W (24,600 BTU/hr) 8,260W (28,200 BTU/hr)
8,240W (28,100 BTU/hr) 9,440W (32,200 BTU/hr)
Operating Temperature
0°C to 40°C
Operating Relative Humidity
5% - 95%
Units Per Initial Cabinet
Rectifiers
0 - 6
Controller
1
Battery Disconnect Modules
1 - 3
DC Distribution
1 - 6
(maximum of 5 with battery disconnect)
Units Per Growth Cabinet
Rectifiers
0 - 6
Battery Disconnect Modules
0 - 1
DC Distribution
1 - 6
(maximum of 5 with battery disconnect)
Table 9-A: Galaxy Power System 4848/100 Specifications (Continued)