Troubleshooting procedure, Purpose, Cabinet alarm – GE Industrial Solutions GPS 4848_100 Users Guide (single rectifier shelf) User Manual
Page 80: Purpose 12-2 cabinet alarm, Figure 12-1: location of cabinet alarm light and, Controller

Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later
12 - 2 Troubleshooting Preparations
Issue 10 February 2008
Troubleshooting Procedure
Purpose
The troubleshooting procedure described below is used when a trouble
condition has been identified and a technician has been dispatched to the
system location as a first and fundamental step in diagnosing and
correcting the problem.
For all trouble conditions, proceed as follows:
Cabinet Alarm
1. Locate the system controller. The controller is typically located in
the cabinet identified as BAY ONE. Because a trouble condition
exists, the red alarm on the top of the cabinet will be illuminated.
See Figure 12-1.).
Figure 12-1: Location of Cabinet Alarm Light and Controller
Galaxy
ESD
WRISTSTR
AP
GRO
UND
ING
POIN
T
Galaxy
Millennium
Controller
Cabinet Alarm Light