13 - 14 Troubleshooting Millennium Systems
Issue 10 February 2008
RECT
MIN
Excess System
Drain
None
None
System load
exceeds shunt
rating.
Call technical support.
RECT
MIN
Limited Recharge
None
None
Rectifier
capacity has
been exceeded.
Install more rectifiers.
RECT
MIN
Rectifier Fail
ALM
ILC
Rectifier not
fully seated.
1. Place the ac circuit
breaker for the
rectifier in the OFF
position.
2. Remove the
rectifier from the
shelf.
3. Wait for 30 seconds
or until all front
panel display LEDs
have extinguished.
4. Replace the
rectifier.
5. Return the ac
breaker to the ON
position.
6. Place the rectifier
ON/STBY switch
into the ON
position.
7. If the problem is not
corrected, replace
the rectifier with a
new one.
Table 13-E: Rectifier Related Alarms (Continued)
(See Figures 12-4 and 12-6)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)