Appendix A - EGD, EtherNet/IP IO Format

26

Data Produced by the Drive

Produced data is located in assembly instance 100 on EtherNet/IP and Consumed Exchange 1(C1) on EGD.

Position Description
Word 0 (16 Bit)

Operation status monitor 1

Word 1 (16 Bit)

Operation status monitor 2

Word 2 (16 Bit)

Output frequency monitor

Operation Status Monitor 1

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

- -

WR

RL

ALM

DEC

ACC

IL

VL

TL

NUV

BRK

INT

EXT

REV

FWD

FWD

1: In forward command

REV

1: In reverse command

EXT

1: In DC breaking or in preparatory excitation

INT 1:

No

output

BRK 1:

In

breaking

NUV

1: DC link voltage is establishment

(Under voltage condition at 0)

TL

1: In torque limiting

VL

1: In voltage limiting

IL

1: In current limiting

ACC 1:

In

acceleration

DEC 1:

In

deceleration

ALM 1:

Alarm

RL

1: Remote (Run command or Frequency command is valid from link)

WR

1: Fieldbus writing right, 0: Keypad writing right

Operation Status Monitor 2

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

- - - - - - - - - - - -

SWM2

RDY

FDT

FAR

FAR

1: Frequency (speed) arrival

FDT

1: Frequency (speed) detection

RDY

1: Ready for operation

SWM2

1: Motor 2 switching

Advertising