Appendix B - Drive Parameters

28

Appendix B - Drive Parameters

Parameter List

This table shows the mapping between Communication No. and drive parameter number. The
Communication No. is used when accessing parameters from the fieldbus.

G11/P11
Code

Communication
No. (Hex)

Description

Data
format

- 0

(0)

-

-

S01

1 (1)

Frequency command

2

- 2

(2)

-

-

-

3 (3)

-

-

-

4 (4)

-

-

S05

5 (5)

Frequency command

5

S06

6 (6)

Operation command

14

S07

7 (7)

Universal Do

15

S08

8 (8)

Accel Time F07

3

S09

9 (9)

Deccel Time F08

3

S10

10 (A)

Driving Torque Limit F40

5

S11

11 (B)

Braking Torque Limit F41

5

S12

12 (C)

Universal Ao

2

-

13 (D)

-

-

- 14

(E) -

-

M01

15 (F)

Frequency command (final)

2

- 16

(10) -

-

- 17

(11) -

-

- 18

(12) -

-

M05

19 (13)

Frequency command (final)

5

M06

20 (14)

Actual frequency

2

M07

21 (15)

Actual value of torque

6

M08

22 (16)

Torque current

6

M09

23 (17)

Output frequency

5

M10

24 (18)

Motor output

5

M11

25 (19)

Output current (rms)

5

M12

26 (1A)

Output voltage (rms)

3

M13

27 (1B)

Operation (final)

14

M14 28

(1C)

Operation state

16

M15

29 (1D)

General-purpose output terminal

15

M16

30 (1E)

Alarm content latest

10

M17

31 (1F)

Alarm content 1st previous

10

M18

32 (20)

Alarm content 2nd previous

10

M19

33 (21)

Alarm content 3rd previous

10

M20

34 (22)

Total operation time

1

M21

35 (23)

DC link voltage

1

- 36

(24) -

-

M23

37 (25)

Type code

17

M24

38 (26)

Capacity code

11

M25

39 (27)

ROM version

1

M26

40 (28)

Processing code in abnormal transmission

20