3 installation, 1 transport, 1 dimensions and weight – GE Industrial Solutions SG Series 400 & 500 Installation Guide User Manual

Page 10: Installation, Transport, Dimensions and weight

Advertising
background image

3 INSTALLATION

3.1 TRANSPORT

Forklift

Crane

Transport UPS only in upright position!

The UPS is packaged on a pallet suitable for handling with
a forklift.

Pay attention to the center of gravity.

The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.

Move the UPS in it’s original package to the final
destination site.

Do not stack other packages on top: This could damage
the UPS.

If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.

Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS
.

NOTE !

Check for sufficient floor and elevator
loading capacity.

Fig. 3.1-1 UPS cabinets moving


3.1.1 Dimensions and weight

Dimensions SG Series 400 & 500

(W x D x H)

80.71 x 33.47 x 76.78 inches

2,050 x 850 x 1,950 mm

SGSU_400

-500_S2_U

PS dimens

ions_GE_0

1US

D

H

W

Fig. 3.1.1-1 UPS cabinet dimensions

Weight SG Series 400 & 500

UPS rating

kVA

Weight

lbs / kg

Floor loading

lbs/sq.ft - kg/m

2

SG Series 400 & 500

5,226 / 2,370

279 / 1,359

P.S.: Weights including the 5th harmonic filter.

Modifications reserved