3.6 UNPACKING
The UPS and Battery Cabinets may be shipped packaged in carton boxes or in wooden crates (if 
requested). 
 
Move the cabinets as close as possible to the final location before removing from the pallet. 
 
If delivered in a wooden crate, remove the cabinet from the pallet with care, because of the heavy 
weight of the equipment. 
 
 
White color
=
without any anomaly
Red color
=
anomaly evidence
Fig. 3.6-1 ShockWatch device
The package of the SG Series 400 & 500 is 
equipped with ShockWatch (indicator for shock), 
and TiltWatch (indicator for overthrow) on the 
outside. 
 
These devices indicate an eventual shock or 
overthrow during transport. 
 
 
 
Whenever these devices show a possible 
anomaly, the UPS shall not be commissioned 
before consulting a “Service Center”.
Fig. 3.6-2 TiltWatch device
 
 
NOTE !
Take care not to damage the UPS when moving by forklift. 
A damaged UPS must never be installed or connected to Utility or Battery! 
In case of any damage sustained during the transport, immediately inform the 
shipping agent! 
A detailed report of the damage is necessary for any indemnity claim. 
 
 