3.8.7 Set-up for SG Series 400 & 500 intended to be operated in eBoost™ Operation Mode

NOTE !

For systems intended to be operated in

eBoost™ Operation Mode

, the

installation shall be protected with suitable surge protection devices (SPDs) on
the AC bus feeding the UPSs.
Please contact your Service Center
for more information.





NOTE !

If an emergency generator set supplies the UPS in case of Mains Failure, and the
system is intended to be operated in

eBoost™ Operation Mode

, eBoost

operation shall be prevented during generator operation.

This can be accomplished by either installing a “Generator ON
” signal (refer to
Section 4.1.4)
or an “eBoost/IEMi control” signal (refer to Section 4.1.6).