3.8.7 Set-up for SG Series 400 & 500 intended to be operated in eBoost™ Operation Mode
NOTE !
For systems intended to be operated in
eBoost™ Operation Mode
, the
installation shall be protected with suitable surge protection devices (SPDs) on 
the AC bus feeding the UPSs. 
Please contact your Service Center for more information. 
 
 
 
 
 
NOTE !
If an emergency generator set supplies the UPS in case of Mains Failure, and the 
system is intended to be operated in 
eBoost™ Operation Mode
, eBoost
operation shall be prevented during generator operation. 
 
This can be accomplished by either installing a “Generator ON” signal (refer to 
Section 4.1.4) or an “eBoost/IEMi control” signal (refer to Section 4.1.6). 