3.8.7 Set-up for SG Series 400 & 500 intended to be operated in eBoost™ Operation Mode
NOTE !
For systems intended to be operated in
eBoost™ Operation Mode
, the
installation shall be protected with suitable surge protection devices (SPDs) on
the AC bus feeding the UPSs.
Please contact your Service Center for more information.
NOTE !
If an emergency generator set supplies the UPS in case of Mains Failure, and the
system is intended to be operated in
eBoost™ Operation Mode
, eBoost
operation shall be prevented during generator operation.
This can be accomplished by either installing a “Generator ON” signal (refer to
Section 4.1.4) or an “eBoost/IEMi control” signal (refer to Section 4.1.6).