Figure 10: Floboy controller.

The “Menu” key provides access to the slide-out
menu which can be touched directly for navigation
and also serves as a reminder of the function keys
definition in the context of the current screen.

The main screen shows pressure, flow, set point
pressure, VFD speed, pumps status, fault status
and provides access to the “Manual” and
“Automatic” mode selection.

Figure 11: Main Screen

The Flow window will show either a flow rate, if an
optional flow meter was purchased with the
system, or a flow indication, indicating “No” for no
flow, and “Yes” for flow> 0.5 ft/sec.

The lower left corner of the screen will display fault
information and other status indications.

PUMP STATUS INDICATORS

show the status of

each pump.

Figure 12: Pump Status Indicators

PRESSURE SET POINT ADJUSTMENT

CAUTION

: Equipment Damage Hazard

Be careful not to set the value too low for the
pump you are using, nuisance overloads can
occur. Also, do not set the value too high for your
systems piping or damage may occur.

Touch the numeric value for the set point:

Figure 13: Pressure Set Point

The password screen for set point will come up.

Figure 14: Set Point Password Entry Screen

Touch the button next to the password value.
Enter “1234” for password and press enter.