Check that you have a foot valve of equal or greater

area than the pump suction piping when you use an

open system with a suction lift.

Prevent clogging by using a strainer at the

suction inlet next to the foot valve. Make sure

that the strainer has an area three times that of

the suction pipe with a mesh hole diameter of

no less than 0.25 in. (0.64 cm).

Check that flexible piping is used on both the suction

and discharge sides of the pump when you use an

isolation base.

Check that a properly sized suction strainer

conforming to NSF/ANSI Standard 50 is installed in

the suction line.

Prevents clogging. Make sure the strainer has

an area three times that of the suction pipe

with a mesh hole diameter of no less than 0.25

in. (0.64 cm).

Check that the pipeline has isolation valves around

the pump and has a drain valve in the suction pipe.

Use Teflon tape sealer or a high quality thread sealant

when you install the suction and discharge

connections to a threaded pump housing.