Xylem IM156 R06 1AB2 & 2AB2, Aquavar ABII Variable Speed Pump Controller User Manual

Page 10

Advertising
background image

10

GREEN LIGHT CODES

Indicator Code Status

Description

Constant

Standby/Low Voltage

Constant Green Light indicates the pump is off. The system is in

Standby mode when there is no flow in the system and the pressure

setting has been reached. The system is in a Low Voltage condition

when the line input voltage drops below 196VAC for 1AB2 and 2AB2

controllers and 98VAC for 1151AB2 controllers.

Blinking

Pump Running

Flashing Green Light indicates the pump is running. If pump is not

running, turn off power to controller and wait 5 minutes. Check

output power connections from controller to motor.

RED LIGHT CODES

Constant

Controller Error

Replace Aquavar ABII Controller

1 Blink

No Water/Loss Of Prime

This fault is indicated if the system pressure drops 5 PSI or more

below the set pressure and the output current is less than 75% of the

motor overload setting for 10 seconds. The system will automatically

restart in 5 minutes. If 3 faults occur in an hour, the system will not

restart and will need to be manually reset. If the problem reoccurs,

please verify supply capacity, pump capacity, proper setting of the

motor overload switches and that there are no restrictions between

the supply and the pump.

2 Blinks

Tank Water-Logged

This warning is indicated if there is a drastic drop in system pressure

in a short amount of time. The warning will not impact operation.

The pump will continue to run. This warning can be caused by low air

pressure in the tank or the tank bladder may have failed. This can also

be caused by extreme changes in flow. The error is cleared each time

the pump starts. If the error reoccurs often, check the air pressure in

the tank. Before checking tank air pressure, turn power to control off

to prevent pump from turning on. Relieve system pressure by opening

a faucet.

3 Blinks

Pressure Sensor Fault

This fault indicates a problem with the pressure sensor feedback.

Verify the connections from the Aquavar ABII Controller to the

pressure sensor. Turn power to controller off and wait 5 minutes.

Remove controller access panel. Be sure sensor cable is wired as

shown in Diagram 4. If cable is wired correctly, check the voltage on

the Input (White) pressure sensor terminal connection in the

Aquavar ABII controller. Using a DC voltmeter, connect the positive

lead to the Input (White) pressure sensor terminal connection, connect

the negative lead to the Com. (Black) pressure sensor terminal

connection. Turn power to controller on. The DC voltage measured

should be in the valid range of 0.5 Vdc to 4.5 Vdc (+/- 0.2 Vdc). If the

voltage is outside this range, replace pressure sensor.

4 Blinks

Pump or Motor Bound

This fault can be caused by mechanical binding from debris in pump

or from an electrical failure in the motor. Verify the error by turning

power to controller off for 1 minute and then on. Pump must be

checked if error persists.

Hazardous

voltage

DANGER

9: TROUBLESHOOTING
General

The Aquavar ABII is a self-diagnosing controller. If a problem occurs, observe the Status Code Indicator Light on the
front of the unit. No Status Code Indicator Light means either no or low input voltage (less than 50 V).

Status Code Indicator Light is not a voltage indicator! Always turn off disconnect switch and circuit
breaker and wait 5 minutes before servicing. High voltage may still remain on controller.

Refer to the status code label on the side of the controller access cover to diagnose system errors. See Diagram 6 for details.

USE THE FOLLOWING TABLE TO HELP TROUBLESHOOT PROBLEMS.

9: TROUBLESHOOTING