Hazardous
voltage
DANGER
When the unit is powered, the Motor Overload and Application Setting Switches are at a high voltage
potential. Always turn off the disconnect switch and circuit breaker and wait 5 minutes before touching
the Motor Overload or Application Setting Switches.
Diagram 3
Diagram 4
Motor Overload Setting
Switches
See chart that follows for
correct switch settings.
Application Switch Setting
See chart that follows for
correct switch settings.
Input
1 Phase
GND
L1
L2 (N)
See Manual For
Switch Settings
Applic.
Type
Output
To Motor
1 2 3 4
1 2 3 4
Pressure
Sensor
Input (Wht)
+5V
(R
ed)
C
om.
(Blk)
T1 T2
T3 GND
Motor
Overload
Setting
Line output to motor.
Correct motor rotation
determines order of colors.
Pressure
Sensor
9K518
Line input power from
2-pole disconnect or
circuit breaker.
GREEN
BLA
CK
BLA
CK
GREEN
WHITE
RED
BLA
CK
BL
UE
RED
BLA
CK
Do not connect 230V to a 115V controller. This will
damage the controller and voids the warranty.
8: DIAGRAMS
Motor Overload and Application Switch Setting
Aquavar ABII Wiring Diagram
8: DIAGRAMS
WARNING