Starting the system – Xylem IM213R04 S-Drive Constant Pressure Aquavar SPD Variable Speed Pump Control User Manual

Page 16

Advertising
background image

Page 16

Section 7

(continued)

Setting the Motor Overload Switches
The Motor Overload Setting Switches adjust the level of motor overload current
protection necessary to protect the motor in case of an over current condition.

Bank 1 switches 1, 2 and 3 allow adjustment of the motor overload setting. These
switches adjust the motor overload protection as a percentage of the full load
output current rating of the controller. Choose a motor overload setting that meets
or is less than the motor’s SFA rating. For example, if the full load output current
rating of the controller is 37A and the motor SFA rating is 33A, the motor overload
setting should be set to 85% (33A/37A = 89%, next lowest setting is 85%).

In applications where the pump and motor are not used to the full capacity the
system may not draw current close to the motor’s SFA rating. In this case choose a
motor overload setting that is close to the actual full load running current.

NOTE

If single phase input power is used the motor overload switches must be set to
50% or lower or nuisance input phase loss errors can result.

The chart below shows the motor overload setting for each model.

STARTING THE SYSTEM

Supply

Voltage

Frame

Size

Model

Number

Motor Overload Setting

100%

95%

90%

85%

80%

70%

50%

40%

208/230

1

SPD20050

17.8

16.9

16.0

15.1

14.2

12.5

8.9

7.1

SPD20050F

2

SPD20075

26.4

25.1

23.8

22.4

21.1

18.5

13.2

10.6

SPD20075F

SPD20100

37.0

35.2

33.3

31.5

29.6

25.9

18.5

14.8

SPD20100F

3

SPD20150

47.4

45.0

42.7

40.3

37.9

33.2

23.7

19.0

SPD20150F

SPD20200

60.6

57.6

54.5

51.5

48.5

42.4

30.3

24.2

SPD20200F

4

SPD20250

76.0

72.2

68.4

64.6

60.8

53.2

38.0

30.4

SPD20250F

SPD20300

94.0

89.3

84.6

79.9

75.2

65.8

47.0

37.6

SPD20300F

460

1

SPD40050

8.9

8.5

8.0

7.6

7.1

6.2

4.5

3.6

SPD40050F

SPD40075

13.2

12.5

11.9

11.2

10.6

9.2

6.6

5.3

SPD40075F

2

SPD40100

18.5

17.6

16.7

15.7

14.8

13.0

9.3

7.4

SPD40100F

SPD40150

23.7

22.5

21.3

20.1

19.0

16.6

11.9

9.5

SPD40150F

SPD40200

30.3

28.8

27.3

25.8

24.2

21.2

15.2

12.1

SPD40200F

3

SPD40250

37.5

35.6

33.8

31.9

30.0

26.3

18.8

15.0

SPD40250F

SPD40300

47.0

44.7

42.3

40.0

37.6

32.9

23.5

18.8

SPD40300F

Advertising