Hazardous

voltage

DANGER

Section 9

General
The Aquavar SPD drives are self-diagnosing controllers. If a problem occurs, observe the Status Code Indicator
Light on the front of the unit. No Status Code Indicator Light means either no or low input voltage (less than
140Vac).

DANGER

Status Code Indicator Light is not a voltage indicator! Always turn off disconnect switch and
circuit breaker and wait 5 minutes before servicing. High voltage may still remain on controller.

Refer to the status code label on the side of the controller access cover to diagnose system errors.

See the following diagram.

Use the following table to help troubleshoot problems.

Red Flashes

Fault Code

Restart Action

Constant

Replace Controller

Controller will not restart. Power must be reset to clear the fault.

2 Blinks

No Water / Loss of Prime

Controller will restart automatically according to the No Water Restart
Time switches (switches 3&4 of bank 2).

3 Blinks

Sensor Fault

Controller will restart automatically when the sensor signal is within the
valid operating range.

4 Blinks

Pump or Motor Bound

Controller will restart automatically 5 times. After 5 faults the power
must be reset to clear the fault.

5 Blinks

Short Circuit / Ground Fault

Controller will not restart. Power must be reset to clear the fault.

6 Blinks

Input Phase Loss

Controller will restart automatically 5 times. After 5 faults the power
must be reset to clear the fault.

7 Blinks

Temperature

Controller will restart automatically when temperature is within the
operating range of the controller.

8 Blinks

Over Voltage

Controller will restart automatically when the input voltage is within the
operating range of the controller.

9 Blinks

Motor Overload

Controller will restart automatically.