Pump Priming

Refer to your pump operation manual for instructions on pump priming. Ensure suction valve is open
before start up.

Run Test

WARNING

DO NOT APPLY POWER TO THE AQUABOOST CONTROLLER OR PUMP UNTIL ELECTRICAL
CONNECTIONS HAVE BEEN REVIEWED BY A QUALIFIED ELECTRICIAN AND MEET ALL AP-
PLICABLE NATIONAL, STATE AND LOCAL CODE REQUIREMENTS.

Instructions

1) Close discharge valve. Make sure the discharge valve is closed. Apply power to the
AquaBoost

Controller.

2) Start the pump with the push button on the front plate of the AquaBoost Controller.
3) Stop the pump after determining rotation by pushing the .
4) If rotation is incorrect, turn off all power to the AquaBoost, open the motor conduit box and ex
change any two lead wires. Close the conduit box and reapply power.

Change Pressure

1) Start the pump with the push button on the front plate of the AquaBoost Controller.
2) Then press the and buttons together for more than 3 seconds.
3) The LED color changes to orange.
4) Now you could change the pressure with the and buttons. The set pressure is read off a
gauge on the pump discharge.

WARNING

DO NOT SET THE REQUIRED PRESSURE FOR MORE THAN 80 PSI SINCE THIS CAN EXCEDE
THE CAPABILITY OF YOUR PLUMBING SYSTEM AND TANK. SERIOUS PROPERTY DAMAGE
OR PERSONAL INJURY COULD RESULT.

5) If there is no change to the setting for more than 5 seconds, the AquaBoost Controller returns to
normal operation automatically, and the new required pressure is stored.
6) The pump can only be STARTED with the button or STOPPED with the button. Both buttons
are on the front plate of the AquaBoost Controller.
LED description
Green Solid – Motor is not running. The unit is stopped with the button on the front plate.
Green Slow Flashing – Controller is active, but the motor has stopped.
Green Fast Flashing – Motor is running.
Red Solid – Error.
Red Flashing – Fatal error (AquaBoost Controller has to be disconnected from the power supply).

Installation Procedures