Xiv. appendix a: terminal strip diagram – Xylem FC220 OPEN CHANNEL FLOW MONITOR User Manual

Page 21

Advertising
background image

Global Water

800-876-1172

globalw.com

- 21 -

XIV. Appendix A: Terminal Strip Diagram

POWER IN:
V+

12VDC or 18-24VDC Input

V+

12VDC or 18-24VDC Input

12VDC Input:

SW7 OFF, SW8 ON

18-24VDC Input: SW7 ON, SW8 OFF

GND

Power Supply and System Ground

GND

Power Supply and System Ground


SENSOR IN:
V+

Sensor Power

12VDC Sensor Power:

SW1 ON, SW2 OFF

18-24VDC Sensor Power:

SW1 OFF, SW2 ON

(18VDC Power Input Only)

IN

Sensor Input

Sensor Power Continuous: SW3 ON

Sensor Power Switched: SW3 OFF (Power Saving Mode)

4-20mA Sensors: SW4 ON, SW5 ON

0-5VDC Sensors: SW4 OFF, SW5 ON

0-1VDC Sensors: SW4 OFF, SW5 OFF


4-20mA:
OUT

4-20mA Output

GND

Power Supply and System Ground, 4-20mA return Path


RELAY 1-4:

Advertising