Manual, Pasiv ma input – Xylem Expert 3400 User Manual

Page 7

Advertising
background image

7

Manual

Manual Expert 1400/3400 GB 0704

MJK Automation A/S
Byageren 7
DK-2850 Naerum
Denmark
Tel.: +45 45 56 06 56
Fax: +45 45 56 06 46
[email protected]
www.mjk.com

Explosion hazardous zone
The insulation between the intrinsic safe circuit and the enclosure withstands 500 VAC.

Isolator
The KFD0-CS-Ex1.50P isolator (MJK part no.: 202993) which supplies the pressure transmitter through a galvanic sepa-

rator so neither current nor voltage exceeds the specified limits.

Zener barrier
The Z788 Zener Barrier (MJK part no. 202995) has a safety fuse which will blow if the current exceeds the limit.
The voltage protection in the Zener barrier contains a number of zener diodes, which are connected from each signal

cable to ground.

Hazardous area

Safe area

Isolator
202993

1 +

2 -

POWER SUPPLY 515

200100

24VDC

-

7

24VDC

+
6

230VAC

N

3

230VAC

L
1

Pasiv

mA input

AI

+

AI

-

230 VAC

KFD0-CS-Ex1.50P isolator

+

Wire 1

Red

-

Wire 2

Brown

shield

Wire 3

black

11 (+)

12 (-)

Safe area

Hazardous area

POWER SUPPLY 515

200100

24VDC

-

7

24VDC

+
6

230VAC

N

3

230VAC

L
1

Pasiv

mA input

AI

-

AI

+

230 VAC

+

Wire 1

Red

-

Wire 2

Brown

shield

Wire 3

black

1

3

2

8

Zener barriere

202995

4

7

Z788 Zener Barrier