Communication protocol Serie30

Page 16/37

4.10

Device Operation Command List

compatible with Class.Group-Version = 5.20-10.XX and later

Writing only allowed with F16 (write cycle with 2 registers)

This address range is NOT readable

corresponding functionality to Keller Bus function F95

Some bytes of the message are fixed, see following frame layout:

Request:

DevAddr

0x10

0xFF

StAdd L

0x00

0x02

0x04

B3

B2

B1

B0

CRC16 L CRC16 H

Response:

DevAddr

0x10

0xFF

StAdd L

0x00

0x02

CRC16_L CRC16_H

MODBUS StAdd

(0xHILO)

Read/

Write

Reg.

Name

DESCRIPTION

0xFF00

W

Set Zero P1

The zero point value from P1 is calculated, that the current measured value equals the

floating point number specified.

0xFF02

W

Reset Zero P1 Zero Point Value from P1 is set to default (Coeff-No. 64 = 0.0)

0xFF04

W

Set Zero P2

The zero point value from P2 is calculated, that the current measured value equals the

floating point number specified.

0xFF06

W

Reset Zero P2 Zero Point Value from P2 is set to default (Coeff-No. 66 = 0.0)

0xFF08

-

-

0xFF0A

-

-

0xFF0C

W

Set Zero CH0

The zero point value from CH0 is calculated, that the current measured value equals the

floating point number specified.

only available in devices of Class.Group 5.20.

0xFF0E

W

Reset Zero CH0 Zero Point Value from CH0 is set to default (Coeff-No. 70 = 0.0)

only available in devices of Class.Group 5.20.