Communication protocol Serie30
Page 23/37
5.6
Function 48 : Initialise and release
Request:
DevAddr
48
CRC16_H
CRC16_L
Response:
DevAddr
48
Class
Group
Year
Week
BUF
STAT
CRC16_H
CRC16_L
Exception error:
3
If message length is incorrect
Note:
Each time the device is switched on by applying the supply voltage or after a break in the power supply, the device must be
initialised via this function. Calling a different function will lead to exception error 32.
The following information is returned:
Class
Device ID code
5:
Series 30 digital pressure transmitter (33, 35, 36, 39)
Group
Subdivision within a device class
1:
Series 30 transmitter from 1999 or later
20:
Series 30 transmitter from 2002 or later
The differences between these devices are defined in italics in the functions.
Year, Week
Firmware version
BUF
Length of the internal receive buffer
STAT
Status information
0:
Device addressed for first time after switching on.
1:
Device was already initialised