Communication protocol Serie30

Page 11/37

4.6

Function 6: MODBUS Single Register Write

This function has the same functionality as F16, but writes only 1 register.

•

Function is implemented in devices Class.Group-Version = 5.20-10.XX and later

•

A register contains 2 bytes (16 bit).

•

Use this function for single configuration steps, cause the returned error is easily distinguishable from other register

writes.

•

Note that single register operations are not allowed in the address ranges 0x03XX and 0xFFXX.

Request:

DevAddr

0x06

StAdd H StAdd L

Data H Data L CRC16_L CRC16_H

Response:

DevAddr

0x06

StAdd H StAdd L

Data H Data L CRC16_L CRC16_H

Error:

DevAddr

0x86

Error

CRC16_L CRC16_H

Error codes:

2

Illegal data address

- address not accessible by function 6

- Start-address not defined (for writing)

3

Illegal data value

- frame length incorrect

4

Slave Device Failure

- The data written is outside the defined data range

4.7

Function 8: MODBUS Echo Test

This function may be used to perform a quick line check. It just returns the data received.

•

Function is implemented in devices Class.Group-Version = 5.20-10.XX and later

•

Data may be any 2 byte value

Request:

DevAddr

0x08

0x00

0x00

Data H Data L CRC16_L CRC16_H

Response:

DevAddr

0x08

0x00

0x00

Data H Data L CRC16_L CRC16_H

Error:

DevAddr

0x88

Error

CRC16_L CRC16_H

Error codes:

3

Illegal data value:

- The data following the function code was not the fixed data (0x00, 0x00).