Installation, Series 42s series 42s-n – Xylem MM 231F Series 42/42S Low Water Cut-Offs/Pump Controllers User Manual

Page 3

Advertising
background image

3

1"

The 42S and 42S-N controls are
installed so that the horizontal cast line
on the body is 1

a

a” (35mm) below the

boiler’s normal water level, but not
lower than the lowest, safe permissi-
ble water level, as determined by the
boiler manufacturer.

The 42S-A controls are installed in boil-
er’s gauge glass tappings. The horizontal
cast line should be approximately 1” (25
mm) above
the bottom of the glass.
Verify that this level is not below the
lowest, safe permissible water level,
as determined by the boiler manufac-
turer.

STEP 1 - Determine the Elevation at Which the
Low Water Cut-Off/Pump Controller Must be Installed

INSTALLATION –

TOOLS NEEDED:
Two (2) pipe wrenches, one (1) flathead screw
driver, and pipe sealing compound.

IMPORTANT: Follow the boiler manufacturer's
instructions along with all applicable codes and
ordinances for piping, blow down valve and water
gauge glass requirements.

1

3

/

8

"

STEAM EQUALIZING PIPE

VERTICAL EQUALIZING PIPE

BLOW DOWN VALVE

NORMAL BOILER
WATER LINE

LOW WATER
CUT-OFF/PUMP CONTROLLER

BURNER CUT-OFF
LEVEL AT CAST LINE

LOWEST
PERMISSIBLE
WATER LEVEL

(35mm)

WATER

EQUALIZING

PIPE

STEAM EQUALIZING PIPE

VERTICAL EQUALIZING PIPE

BLOW DOWN VALVE

LOW WATER
CUT-OFF/PUMP CONTROLLER

BURNER CUT-OFF
LEVEL AT CAST LINE

WATER

EQUALIZING

PIPE

1

3

/

8

"

NORMAL BOILER
WATER LINE

LOWEST
PERMISSIBLE
WATER LEVEL

(35mm)

Series 42S

Series 42S-N