Wiring diagrams – Xylem MM 231F Series 42/42S Low Water Cut-Offs/Pump Controllers User Manual

Page 8

Advertising
background image

WIRING DIAGRAMS

Low Water Cut-Off Only

1. Main Line Switch - For burner circuits within the

switch’s electrical rating.

Pump Control Only

1. Install a starter or relay in pump control circuit,

as shown, to prevent damage to snap switch
and help insure proper switch/control operation.
Failure to do so may shorten the life of the
switch when actual amperage exceeds switch rating.

2. Connect wires from holding coil of pump starter

or relay to terminals 1 and 2 as shown.

NOTE: To help insure most effective operation,
balance boiler feed pump(s) to deliver required water
feed rate to match boiler steaming requirements.

1. Main Line Switch - For burner circuits within

the switch’s electrical rating.

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

1 2

5 6

SEE PUMP

CONTROL

CIRCUIT

TO BURNER CONTROL CIRCUIT

HOT

1 2

5 6

LOAD

LINE

SEE PUMP

CONTROL

CIRCUIT

1 2

5 6

LOAD

LINE

1 2

5 6

LOAD

LINE

OR

OR

Combination Pump Control, Low Water Cut-Off and Alarm

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

8

LINE

LOAD

1 2

5 6

Advertising