For 42s-a control, Step 2 - installation – Xylem MM 231F Series 42/42S Low Water Cut-Offs/Pump Controllers User Manual

Page 4

Advertising
background image

4

For 42S-A Control

H

INVERTED “Y” CASTING

Note:
Reverse union
nuts, packing
and plug.
Tighten top
nut securely.

J

H

G

F

J

c. Determine the position of the black ‘Y’ casting (H).

If gauge glass tappings (F) and (G) are less
than 10

5

8

" (270 mm) apart, install the black

‘Y’ casting (H) as depicted in the diagram to the
top right.

OR

If gauge glass tappings (F) and (G) are
greater than 10

5

8

" (270 mm) apart, invert

the black ‘Y’ casting (H) as depicted in the
diagram to the bottom right.

OR

If gauge glass tappings (F) and (G) are
greater than 14" (356 mm) apart, invert the
black ‘Y’ casting (H) as depicted in the diagram
to the bottom right and install a longer brass nipple (J).

C

a. Drain the water in the boiler until the level falls below the lower

gauge glass connection (C). Allow the boiler to cool to 80˚F
(27 ˚C) and allow the pressure to release to 0 psi (0 bar).

D

E

b. Remove the water glass (D) and gauge glass connections (E)

from the boiler.

STEP 2 - Installation

B

A

a. Using a pipe wrench, unscrew shipping block (A) from

upper 1” NPT tapping (B) of the control body.