For 42S Control

DD

CC

NN

a. Mount and pipe control (CC) on vertical equalizing

pipes (DD) at the required elevation as determined
in Step 1.

b. Install a full ported ball valve (NN) directly below the

lower cross of the water (lower) equalizing line.

For 42S-N Control

JJ

EE

HH

GG

FF

NN

a. Install fitting (EE) provided in top 1” NPT tapping.

Orient 1/2” NPT tapping (FF) with 1/2” tapping on
control (GG).

b. Mount and pipe control (HH) on vertical equalizing

pipes (JJ) at the required elevation as
determined in Step 1.

c. Install gauge glass and other trim such as

pressure gauges or pressure controls following
manufacturer’s instructions. Note: These items
are not provided and must be purchased
separately.

d. Install pipe plugs in all unused tappings on

control body and fittings.

e. Install a full ported ball valve (NN) directly below

the lower cross of the water (lower) equalizing line.