Xylem MM 244B Series 42S Replacement Snap Switch Assembly User Manual

Page 10

Advertising
background image

10

RULER

CAST
LINE

LEVEL

3"

(76.2mm)

2"

(50.8mm)

1"

(25.4mm)

Casting
Cut-Off
Line

1"

(25.4mm)

TOP

SECTION 3 - Checking Switch Settings at 0 Pressure

2. Hold the ruler against the side of the gauge glass

in a position so the Cast Line mark is on the same
level as the cast line on the float chamber of the
control (a carpenter's level should be used to
insure the cast line on the float chamber is on the
same plane as the one on the marker).

3. Once the marker is properly positioned, tape it to

the gauge glass.

PUMP OFF

PUMP ON

BURNER
CUT-OFF LEVEL
AT CAST LINE

4a. Drain the water level in the boiler until the pump

turns on. Note the level at which the pump turns on
and then turns off. Verify that pump settings are
acceptable.

b. Turn the pump off.

BURNER

ON

BURNER

OFF

NORMAL BOILER

WATER LINE

BURNER
CUT-OFF LEVEL
AT CAST LINE

7/8

"

(22mm)

5a. Drain the water level in the boiler until the burner turns

off. Observe the burner off point.

b. Turn the pump back on and observe the Burner On

point as the boiler fills with water. In the case of manual
reset models, try resetting the burner switch as close as
possible to the Burner On point as shown in chart for
the control and as measured on the switch level ruler.
Verify that burner settings are acceptable.

2"

(50.8mm)

1"

(25.4mm)

1"

(25.4mm)

3"

(76.2mm)

Casting
Cut-Off
Line

1. Find the "Switching Level Ruler" on page 11,

and cut it out along the indicated lines.

(Not to Scale. Template

located on page 11).

IMPORTANT: All switches have fixed differentials. Adjustment of switches referred to in Sections 2 and 3 are
all based upon Pump Off and Burner Off setpoints. The Pump On and Burner On setpoints are not adjustable.