background image

F

ADD ADHESIVE HERE

8

BURNER
SET SCREW

BURNER
SWITCH

E

4b. If the cut-off point does not match the one

shown in chart for the control (page 3) as
measured on the "Switch Level Ruler," using
an awl, dig the inspection lacquer out of the
socket in the set screw (E) above the burner
switch in the actuator assembly.

c. Using an Allen wrench with a 5/64" hex, turn

the screw 1/4 turn:
- clockwise when viewed from top (if the
“Burner Off” point is too high)
- counterclockwise when viewed from top
(if the “Burner Off” point is too low )

4d. Turn the pump back on, allowing the boiler

to fill with water.

PUMP OFF

PUMP ON

BURNER
CUT-OFF LEVEL
AT CAST LINE

4a. Slowly bring the boiler water level down to

the point at which the burner cuts off. If the
burner does not shut off automatically by the
time the water level reaches 3/8" (9.5mm)
below the cast line on the unit body, shut the
burner off manually.

4f. Repeat steps a. through d. as necessary to

match the Burner Off point specification for
your model.

4 - Setting the Operating Points of the Burner Switch