Installation, Warning – Xylem MM 244B Series 42S Replacement Snap Switch Assembly User Manual

Page 4

Advertising
background image

4

B

3. Remove the cover (B).

LOW WATER

CUT-OFF

TERMINALS

BURNER

SWITCH

PUMP
SWITCH

PUMP CIRCUIT

TERMINALS

4. Mark and remove the pump switch

and burner/alarm switch wires from
terminal block.

OFF

ON

1. Turn the boiler off.

A

2. Allow the boiler to cool to 80˚F (27˚C) and

release the boiler pressure to 0 psi (0 bar).
Drain water in the boiler to a level which is
below the float chamber (A).

INSTALLATION –

SECTION 1 - Switch Bracket Replacement

To prevent electrical shock, turn off the electrical power before making electrical connections.

This low water cut-off must be installed in series with all other limit and operating controls installed on the

boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving

the site.

Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in

property damage, personal injury or death.

!

WARNING