Flow rates – Xylem MM 613F Series FS4-3T General Purpose Liquid Flow Switch User Manual

Page 3

Advertising
background image

FLOW RATES

Settings will vary when used to sense flow of other

fluids.

3

NOTE: DO NOT USE LIQUID FLOW SWITCHES ON SYSTEMS

WITH FLOW VELOCITY GREATER THAN 10 FEET (3M)

PER SECOND.

Values are ± 10%

Flow Rates

Pipe

Mode of Operation

Model

Size NPT

Flow

No Flow

Number

in. (mm)

Settings

gpm (lpm)

gpm (lpm)

Factory or

FS4-3T1-

3

4

3

4

(20)

Minimum

4.4

(16.7)

2.6

(9.8)

Maximum

10.5 (39.7)

9.8 (37.1)

Factory or

FS4-3T2-

3

4

3

4

(20)

Minimum

3.7

(14)

2.2

(8.3)

16.62

Maximum

8.9

(33.7)

8.3 (31.4)

(63)

Factory or

FS4-3T3-

3

4

3

4

(20)

Minimum

2

(7.6)

1.2

(4.5)

Maximum

4.5

(17)

4.1 (15.5)

Factory or

FS4-3T1-1

1

(25)

Minimum

5

(18.9)

3.2 (12.1)

Maximum

11.5 (43.5)

11 (41.6)

Factory or

FS4-3T2-1

1

(25)

Minimum

4.8

(18.1)

2.9

(11)

27

Maximum

10.1 (38.2)

9.4 (35.6)

(102)

Factory or

FS4-3T3-1

1

(25)

Minimum

2

(7.6)

1.2

(4.5)

Maximum

4.5

(17)

4.1 (15.5)

Max. Flow

Rate gpm
(lpm) w/o

Paddle Damage

calculated using clean water in a horizontal pipe.

Flow rates required to activate the flow switch

are shown in chart below.These values were

NOTE: THIS PRODUCT IS NOT INTENDED FOR USE IN

POTABLE WATER APPLICATIONS.