INSTALLATION –

STEP 1 - Determine the Location of the Flow Switch

D

FLOW

3/4

" or 1"

PIPE

5 x D

MINIMUM

5 x D

MINIMUM

D= PIPE DIAMETER

• The flow switch

should be located in a horizontal

section of pipe where there is a straight horizontal run

of at least 5 pipe diameters on each side of the flo w

switch. The flow switch may be installed in a vertical

pipe if the flow is in the upward direction.

• The flow switch

must be installed in the upright

position as shown with arrow mark on side of casting

in the same direction as fluid will flo w.

• Some system conditions that require more than 5 pipe

diameters are high viscosity fluid and high fluid v elocity.

• The flow switch should be installed in the pump suction

piping when spring-loaded check valves and/or other

closed coupled accessories are installed in the pump

discharge piping.

STEP 2 - Connecting the Flow Switch to Pipe

a. Apply pipe sealing compound or PTFE tape to the

NOTE: Do not apply sealant to first threads as this

switch is grounded (earthed) via the pipe mounting.

FLOW

b. Insert pipe threads into flow switch and turn 2

or 3 times until tight.

• Place one pipe wrench on base of flo w

switch and one wrench on connecting piping.

Tighten to following torque values.

- 47 ft•lb (64 N•m) for 3/4” pipe

- 63 ft•lb (85 N•m) for 1” pipe

• Repeat to connect pipe to opposite side of

flow switch.

PTFE

pipe threads.