Xylem MM 613F Series FS4-3T General Purpose Liquid Flow Switch User Manual

Page 7

Advertising
background image

7

a. Place cover on flow switch and turn on power. Initiate fluid

flow through the system. Observe the device being

activated by the flow switch to determine if device is

operating as required.

b. Turn off fluid flow to determine if device is operating

as required.

c. Repeat initiating and turning off fluid flow several times to

test flow switch and device for proper operation.

- If operating as required, put system into ser vice.

- If not operating as required, flow switch may need

to be adjusted.

OFF

ON

STEP 4 - Testing

SECTION 5 - Adjustment

ADJUSTING SCREW

FLOW

OPENS

CIRCUIT

FLOW

CLOSES

CIRCUIT

COMMON

1

2

3

Adjustment is necessary only if required flow/no

flow setpoints are

above factory set minimum.

a. Turn off power. Remove electric enclosure

cover.

b. Turn adjusting screw clockwise (1/8 turn) to

increase setpoint.

c. Place the cover on the flow switch and turn on

power.

d. Test the operation of the flow switch after

each adjustment.

IMPORTANT: Do not attempt to lower flow switch

setpoint from original factory minimum setting.

Lowering (turning adjusting screw counterclock-

wise) the setpoint from original factory setting

may cause erratic flow switch operation.