a. Cover Removal and Installation Procedure

• Using a flathead screwdriver, loosen but do not remove

the two cover screws and remove the cover (A).

• Place the cover on the flow switch sliding the slots

behind the two loose cover screws. Push the cover

down into the flow switch and using a flat blade screw-

driver, tighten the cover screws to a torque of 10 lb•in

(1.13 N•m).

STEP 3 - Electrical Installation

• To prevent electrical shock, turn off the electrical power before making electrical connections.
• To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of

167°F (75°C) if the liquid’s temperature exceeds 180°F (82°C).

• To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the

terminals.

• Make sure flow switch electrical cover is secured before turning on electric power.

Failure to follow this warning could cause property damage, personal injury or death.

!

WARNING

b. Electrical Conduit Connection
• Connect electric conduit to flow switch electrical enclosure.

• Follow accepted electrical practices when installing fittings

and making connections.

• Refer to and follow local codes and standards when

selecting the types of electrical fittings and conduit to

connect to flow switch.