Xylem WL16 WATER LEVEL LOGGERS User Manual

Page 16

Advertising
background image

Global Water

800-876-1172 globalw.com

- 16 -

Bar Graphs: The bar graphs show a visual representation of the most recent data

reading taken by using the Sample Continuously or Get Sample functions. The

upper and lower limits of the display are defined by the user as discussed in detail

later.

Numerical Reading: The numerical reading at the bottom of the bar graph shows

the actual data reading and is updated at the same time as the bar graph.

Successive numerical readings taken by using Sample Continuously or Get Sample

are shown in a list below the bar, up to 5.

Alarm 1: This field shows the time that the logger is set to start logging. The start

alarm is a 24-hour timer which will initiate logging, when enabled, at the next

occurrence of that time.

Alarm 2: This field shows the time that the logger is set to stop logging. The stop

alarm is a 24-hour timer which will halt logging, when enabled, at the next occurrence

of that time after the logger has started recording. If the Alarm 1 timer is

set to initiate logging, the Alarm 2 timer will halt logging at the next occurrence of the

Alarm 2 time after the logger has been started by Alarm 1. If the Alarm 1 timer is not

enabled, the Alarm 2 timer will halt the logger on the next occurrence of that time.

Note: The alarm start and stop cycle is a one time occurrence. Once stopped

by the Alarm 2 timer, the logger will not resume logging again until the logger

is reprogrammed. Reprogramming the logger with the timers enabled will

restart the alarm cycle. Reprogramming the logger with the timers disabled

will return the logger to a normal logging state

Use care when programming the alarm times. If left enabled, changing and

reprogramming any of the setup parameters will restart the alarm timers and

could cause the logger to stop recording.

Advertising