Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Setup Programming Guide User Manual
Page 139

TS-TPI Setup Programming
Page
23 - 5
23
—
PUMP N Menu
continued —
TYPE
“READ ONLY”
Here is the PUMP N menu.
Press the
M2
key to display the TYPE
PUMP N “READ ONLY” field ....
In this example, type ‘VFC’ is displayed ....
There are five types of controllers-
VFC, SC, SCIII, SCI and VFCIV.
— Press the CANCEL key to return to the PUMP N menu —
— Proceed to the next menu - GROUP —
GROUP
“READ ONLY”
Here is the PUMP N menu.
Press the
M3
key to display the GROUP
PUMP N “READ ONLY” field ....
In this example, group “2” is displayed ....
The group value may be 1 to 4. This menu
item defines which group or TS-TPI port
number is attached to which pump. A value
of 1, 2, 3 or 4 will indicate that the controller
is on that port. Any Line Leak Detectors will
be on Group 1, therefore the first pump group
is 2.
— Press the CANCEL key to return to the PUMP N menu —
— Proceed to the next menu - ADDRESS —
GROUP PUMP 1
READ ONLY
2
TYPE PUMP N
READ ONLY
V F C
PUMP N
(MORE)