Franklin Fueling Systems TSP-UHS User Manual

Overview

Advertising
background image

1

Overview

The TSP-UHS is a Standard sensor that is used to detect

the loss of a liquid in the normally solution-filled sensor

reservoir connected to the interstitial areas of double-wall

dispenser sumps. The sensor is supplied with electrical

connectors, 25 feet of cable, and a cord-grip fitting (see

diagrams). The TSP-UHS uses magnetic-float / reed-switch

technology (the sensor must be suspended vertically so

the float can freely follow the level of a liquid).
When the float drops more than 3/4 of an inch, the

magnetically sensitive reed switch will open. An open

circuit is recognized as an alarm-condition at the

intrinsically safe (I.S) leak detection circuits of the FFS

(Franklin Fueling Systems) ATG console.

Testing the TSP-UHS

This device can be tested by lifting the sensor from the

sensor reservoir. This will cause an alarm at the ATG

console. Test the sensor for proper operation on a yearly

basis, or more frequently per local code.

Materials Required

Optional: TSP-DB1 Epoxy Seal kit for no-strip electrical

•

connectors – recommended for sites: within flood zones,

high groundwater tables, with poor drainage, or when

Junction Boxes are not used

1/2 or 3/4 inch NPT (National Pipe Thread, tapered),

•

Rigid Metal Conduit (RMC) or nonmetallic (PVC) conduit

if allowed by local code

EYS Seal fittings and Epoxy to fill the fitting after

•

operational testing is completed (as required).

Weatherproof Junction Box, gasket, and cover, plus

•

a 3/4 to 1/2 inch NPT reducing bushing if 1/2 inch

RMC is used. Refer to the ATG Installation Guide for

recommended electrical Junction Boxes

Wire: THHN, TFFN or THWN, 18 AWG, White & Black,

•

or Alpha Cable # 58411, 0.114 O.D., 1,500 feet (457

meters) max. length. If using nonmetallic (PVC) conduit,

Alpha Wire P/N 58411 (2.8 mm) 0.112” O.D. must be

used (INCON P / N 600-0062).

Slip joint pliers to seat the no-strip, self-sealing wire

•

connectors. Connectors are supplied with the sensor

• UL Classified Thread Sealant or pipe dope.

TSP-UHS Universal Hydrostatic Sensor

Installation Instructions

Magnetic Reed Float Switch

opens when float moves

down 0.75” (19 mm)

N.C.

Normal Liquid Level

Figure 1: TSP-UHS Overview